Inspection program
FDNY fire protection tests for NYC buildings
It depends on the systems in the building. Sprinklers get a monthly visual inspection, standpipes and fire department connections a 5-year hydrostatic test, and fire alarms the NFPA 72 schedule plus a 5-year retest. Fire pumps, generators, smoke control, ARC radio and extinguishers each add their own cycle. Each test is done by a holder of the matching FDNY certificate.
| Line | Price |
|---|---|
| Sprinkler and standpipe annual, high-rise | Get a price |
| Standpipe 5-year test, per riser | Get a price |
| Fire alarm annual test, 150 to 400 devices | Get a price |
| Fire pump annual flow test, per pump | Get a price |
| Generator annual load-bank test | Get a price |
| Extinguisher annual service | Get a price |
| Emergency light 90-minute test | Get a price |
Status: information for residential buildings, quote for commercial. Commercial buildings can request a per-system price. A tower can request one quote listing each system and test.
Which tests your building has
A building owes only the tests for the systems it has. A high-rise building has an occupied floor more than 75 feet above fire department vehicle access.
- Sprinklers: monthly visual inspection, quarterly waterflow alarm tests, a yearly main drain test and a 5-year test of the fire department connection. Sprinkler inspection.
- Standpipes: hydrostatic pressure test and flow test at least every 5 years. Standpipe 5-year test.
- Fire alarms: NFPA 72 schedules, smoke detectors cleaned every six months, full retest every five years. Fire alarm inspection.
- Fire pumps: weekly no-flow run and an annual flow test of each pump. Fire pump test.
- Generators and emergency lighting: load tests under NFPA 110, plus monthly and annual emergency light tests. Generator test.
- Smoke control and elevator recall: dedicated systems tested semiannually, recall tested monthly. Smoke control and recall.
- ARC radio: a test every 12 months and a recertification every fifth year. In-building radio.
- Extinguishers: monthly check and annual service under NFPA 10. Extinguisher service.
- Kitchen exhaust: inspection by an approved cleaning company every 3 months, usually the restaurant tenant's job. Kitchen exhaust.
Plans and staff are a separate family: fire safety and emergency plans and the Fire and Life Safety Director.
Which FDNY certificate each test needs
Inspection and testing of sprinkler, standpipe and fire alarm systems is done personally by a certificate of fitness holder.
- Sprinklers: S-12. Testing and repair also take a Master Fire Suppression Piping Contractor or Master Plumber.
- Standpipes: S-13, or S-14 for multi-zone systems.
- Fire alarms: S-97 or S-98 for testing and servicing.
- ARC radio: B-03.
- Extinguishers: W-96.
- Kitchen exhaust: W-64 technicians.
How far ahead to book witnessed tests
FDNY lists 40 to 60 business days for a sprinkler or standpipe test request and 40 to 70 for a fire alarm inspection request. We don’t promise a deadline. If a firm cannot take your job, nothing is charged.
Records
Inspection, test and maintenance records are kept for at least 3 years unless a different period applies, and FDNY may require some to be filed. We send the report and photos for your records.
FDNY fees
FDNY charges $365 to witness a standpipe test with one connection and $320 for a sprinkler system with one connection. Witnessed tests without a set fee are $210 an hour per inspector. Failing to give access for a scheduled FDNY test costs $105.
Penalties
- Fire protection systems: $950 for a first violation, $2,375 for a repeat.
- Inspection and testing: $600 first, $1,500 repeat.
- Recordkeeping: $700 first, $1,750 repeat.
- Certificate of fitness: $750 first, $1,875 repeat.
- False certification: $2,500 first, with no mitigation.
A repeat penalty applies to a second violation of the same kind by the same respondent.
Fixing a violation
An FDNY violation certified corrected on time, with proof FDNY accepts, needs no hearing and carries no civil penalty. We book the licensed firm for the repair and keep the proof on file.
Questions
What FDNY inspections and tests does my building need?
Every sprinklered building needs monthly sprinkler inspections, and every standpipe a 5-year hydrostatic and flow test. Fire alarms follow NFPA 72 with a 5-year retest. Add fire pump, generator, smoke control, ARC radio and extinguisher tests where the building has those systems.