In-building radio (ARC) system tests

The ARC system is the in-building auxiliary radio firefighters use. It is inspected and tested at least once every 12 months, and every fifth year a five-year recertification takes the place of the yearly test. The recertification is done within one continuous 72-hour period. FDNY's B-03 certificate is required to test it.

Status: information only. Keep the yearly test, 5-year recertification and permit in your building records. We do not offer ARC work.

Which buildings need it

A high-rise building has an occupied floor more than 75 feet above fire department vehicle access. Any building that runs an in-building auxiliary radio system needs an FDNY permit to establish and operate it.

Who may test it

Testing is supervised by an ARC system professional certificate holder who also holds an FCC General Radiotelephone Operator License. FDNY's B-03 certificate is required to test the system.

How often

  • Daily: the dedicated ARC radio console is inspected.
  • Every 12 months: inspection and test of the whole system.
  • Every fifth year: a five-year recertification in place of the yearly test, done within one continuous 72-hour period.

Plan the 72-hour window with your tenants and security desk well ahead. Records are kept for at least 3 years.

FDNY permit fee

FDNY's permit fee to maintain and operate an in-building auxiliary radio system is $105.

What we coordinate

Keep the daily check, yearly test, recertification and permit dates in your building records. See the FDNY testing overview.

Questions

What is the FDNY ARC in-building radio test?

A yearly inspection and test of the building's auxiliary radio communication system, replaced every fifth year by a recertification done within 72 continuous hours. A B-03 certificate holder does the testing.