For chief engineers: device tests, access and records

Send us the devices or systems you need tested, the building rules and any access limits. We coordinate the visit and send the reports after we check them. FDNY expects inspection and test records on site for at least three years unless a different period applies.

Inspection cycles by device

Each elevator has its own periodic inspection and CAT1 test, at least three months apart, and its own report windows. Sprinklers and standpipes get a monthly visual inspection by the certificate of fitness holder, standpipes a 5-year hydrostatic and flow test, and every fire alarm system a retest every five years. Fire pumps get a weekly no-flow run and an annual flow test. Cooling towers need a compliance inspection at least every 90 days.

Keep the device or system identifier, last inspection date and next due date in your building records.

Records FDNY and DOB expect on site

  • Sprinkler, standpipe and fire alarm records: kept at least 3 years unless another period is set.
  • Fire alarm log book: a separate book for each calendar year.
  • Standpipe inspection record: posted near the main control valve.
  • Drills, training and plan reviews: in a bound log book or an approved electronic format.
  • Smoke control tests: in a logbook or other approved record.
  • Elevator maintenance log: one per device, on site.
  • Cooling tower records: on site for at least three years.

We send each firm's report, test sheet and filing receipt to you after we check it, so the entry in your book matches the paperwork. The logbooks themselves stay with the building.

Your staff's part

Some routine work stays with building staff who hold the right certificate. An S-95 or director certificate holder may do the daily visual inspection, the monthly manual alarm test and the log book; everything else on the fire alarm takes an S-97 or S-98 holder.

The owner must also name an impairment coordinator for sprinkler, standpipe and fire alarm systems. That is usually you or someone on your team, and it is the name we give firms on fire protection jobs.

Access and after-hours, booked through us

Tell us your building's vendor rules once: visitor logs, badges, escorts, freight elevator, hours, union rules, hot-work and impairment procedures. We send the rules that apply with every job, and firms follow them. You confirm the access window and an on-site contact for each visit; multi-day device series are booked as one series.

Missed access costs money. FDNY charges $105 when nobody gives access for a scheduled inspection or witnessed test, and test requests outside regular hours carry additional off-hour fees.

Lead times for witnessed tests

FDNY lists 40 to 60 business days for sprinkler and standpipe test requests, and 40 to 70 business days for a fire alarm inspection request. The elevator agency must notify DOB at least five calendar days before a CAT3 or CAT5 test. We don’t promise a test date.

Questions

What records does FDNY expect a building to keep on site?

Inspection, test and maintenance records for sprinklers, standpipes and fire alarms, kept at least 3 years, plus a fire alarm log book for each calendar year. Drills and plan reviews go in a bound log book or an approved electronic format, and smoke control tests in a logbook or other approved record. The standpipe inspection record is posted near the main control valve.

Do you replace our fire protection contractor?

No. You can keep your contractor. If you request fire protection work through us, the firm must hold the required FDNY credentials.