Inspection program
Sprinkler inspection and testing in NYC
A NYC sprinkler system gets a visual inspection every month by a certificate of fitness holder, following NFPA 25. Waterflow alarms are tested quarterly, the main drain every year, and the fire department connection gets a hydrostatic test at least every 5 years. Testing and repair take a licensed master contractor, not only the certificate holder.
| Line | Price |
|---|---|
| Sprinkler and standpipe annual, high-rise | Get a price |
| Sprinkler annual inspection and test, residential | Get a price |
| Sprinkler 5-year connection test, per system | Get a price |
Status: information for residential buildings, quote for commercial. Commercial buildings can request a quote per system.
Which buildings need it
Any building with a sprinkler system. A high-rise building has an occupied floor more than 75 feet above the lowest fire department vehicle access.
Who may do the work
FDNY's S-12 certificate covers people who inspect, test and maintain sprinkler systems. An S-12 holder on their own may do visual inspections only. Testing and repair take a licensed Master Fire Suppression Piping Contractor or Master Plumber who also holds the certificate.
Your own staff can carry part of it. An S-12 holder employed by the owner who also holds an operating engineer licence may do visual inspections, test notification appliances, do daily and weekly routine maintenance and record the results. We book the licensed contractor for the rest.
How often
- Monthly: visual inspection by the certificate holder.
- Quarterly: waterflow alarm and supervisory device tests.
- Yearly: main drain test at each water-based system, and a trip test of each dry pipe valve in warm weather.
- Every 5 years: hydrostatic test of the fire department connection at 100 psig held for at least 20 minutes, gauge replacement or calibration check, and internal inspection of check valves.
Keep at least six spare sprinkler heads on the premises.
Records and filing
Inspection, test and maintenance records are kept for at least 3 years, and FDNY may require some to be filed with it. The 5-year connection test is witnessed by FDNY; requests run 40 to 60 business days, depending on testing volume. We send the report for your records.
FDNY fees
FDNY's periodic test fee for a sprinkler system with one fire department connection is $320. Failing to give access for a scheduled FDNY test costs $105.
Penalties
A fire protection systems violation is $950 for a first violation and $2,375 for a repeat. An inspection and testing violation is $600 first, $1,500 repeat. Missing records count as a recordkeeping violation: $700 first, $1,750 repeat.
When the system is out of service
The owner designates an impairment coordinator for sprinkler, standpipe and fire alarm systems. After four hours out of service, fire watch patrols may only be done by fire guards holding an FDNY certificate. Fire guards come from the building or a guard service; this site does not supply them.
What we coordinate
- The annual inspection and test visit and the 5-year connection test, booked with a licensed contractor that holds the S-12 certificate.
- Coordination of the FDNY test request. We don’t promise a deadline.
- Repairs after a failed test, and the proof FDNY accepts for a correction.
Questions
How often do sprinklers have to be inspected in NYC?
At least once a month, by a certificate of fitness holder, under NFPA 25. Waterflow alarms are tested quarterly, the main drain yearly and the fire department connection at least every 5 years.