Guide
How to choose a fire protection company in NYC
Match the company to the test. Each FDNY test needs a specific certificate of fitness: S-12 for sprinklers, S-13 or S-14 for standpipes, S-97 or S-98 for fire alarms, W-96 for extinguishers, W-64 for kitchen exhaust and B-03 for ARC radio. For sprinkler testing and repair, the company also needs a licensed master contractor.
Which certificate each test needs
- S-12, sprinklers: inspecting, testing and maintaining sprinkler systems. On its own, visual inspections only; testing and repair take a Master Fire Suppression Piping Contractor or Master Plumber with the certificate.
- S-13, standpipes: inspecting, testing and maintaining standpipe systems.
- S-14, multi-zone standpipes: multi-zone systems, which need continuous personal supervision by a certificate holder.
- S-97 or S-98, fire alarms: programming, inspecting, testing and servicing. Nobody else may do it.
- S-95, building staff: supervising the visual inspection of an alarm system without voice communication. S-95 holders may only do the daily visual check, the monthly manual test and the log book.
- S-99, after alarm repairs: the licensed professional who verifies the alarm system works once defects are corrected.
- F-53, voice systems: at least one holder on premises during business hours for each alarm system with one-way voice communication.
- W-96, extinguishers: selling, leasing or servicing portable extinguishers.
- W-64, kitchen exhaust: cleaning technicians, inspecting and cleaning at least every three months.
- B-03, ARC radio: testing the in-building auxiliary radio system.
- F-89, Fire and Life Safety Director: valid at one location for one person.
- F-07, drill conductor: leading fire and emergency drills in buildings that do not require a director.
F-53, S-95, F-89 and F-07 holders are usually your own building staff. The rest belong to the outside company.
The firm types you will deal with
- Sprinkler and standpipe contractor: a Master Fire Suppression Piping Contractor or Master Plumber whose staff hold S-12, S-13 or S-14. It also files the FDNY standpipe test request.
- Fire alarm company: its principal holds an S-97. Commercial and multi-tenant systems are monitored by an approved central station.
- Extinguisher company: W-96 holders, who leave an FDNY-approved tag on each unit.
- Kitchen exhaust cleaner: an approved cleaning company with W-64 technicians, usually hired by the restaurant tenant.
- ARC radio contractor: a B-03 holder who also holds an FCC General Radiotelephone Operator License.
What to check before you hire
- Certificate numbers. Ask for the certificate of the person who will do the work as well as the company's. Inspection and testing is done personally by the certificate holder.
- The master licence. Sprinkler testing and repair need a licensed master contractor on top of the S-12.
- FDNY test day. An S-97 or S-98 holder must be present at any FDNY fire alarm test, and a missed FDNY appointment costs $105.
- Records. Reports kept at least 3 years, and in the form FDNY may ask for.
- Tags and decals. A current proof-of-compliance tag on extinguishers, and an authentic decal on kitchen exhaust work.
- Insurance. On commercial jobs, the firms we book carry general liability insurance at the required limits plus umbrella coverage at the required limit.
A false certification to FDNY carries a $2,500 penalty for a first violation, with no mitigation, so paperwork from an uncertified person is a real risk.
Lead times
FDNY lists 40 to 60 business days for sprinkler and standpipe test requests and 40 to 70 for fire alarm and fire pump requests. A company that promises next week's witnessed test is promising something FDNY controls.
Questions
How do I choose a fire protection company in NYC?
Check that the person doing each test holds the FDNY certificate for it: S-12, S-13 or S-14 for sprinklers and standpipes, S-97 or S-98 for alarms, W-96 for extinguishers. For sprinkler testing and repair, also check for a licensed master contractor. Then ask about FDNY lead times, records and insurance.